| Operation temperature | 
 -40 °C to +70 °C / -40 °F to +158 °F  | 
| Temperature cycling acceptance criteria | 
 Δα ≤ 0,05 dB  | 
| Temperature cycling | 
 -40 °C +70 °C / -40 °F +158 °F  | 
| Temperature cycling test method | 
 IEC 60794-1-22:F1  | 
| Transport / store temperature | 
 -40 °C to +70 °C / -40 °F to +158 °F  | 
| Crush resistance - short term | 
 2000 N/100mm  | 
| Expected lifetime | 
 min. 30 years  | 
| Tensile performance - during installation | 
 4500 N  | 
| Tensile performance - during installation acceptance criteria | 
 Δα ≤ 0,05 dB after test  | 
| Tensile Performance during Installation TestMethod | 
 IEC 60794-1-21:E1  | 
| Repeated bending acceptance criteria | 
 no damage  | 
| Repeated bending test method | 
 IEC 60794-1-21:E6  | 
| Repeated bending | 
 R=20 x cable diameter, 25 cycles  | 
| Cable bend - acceptance criteria | 
 Δα ≤ 0,05 dB after test, no damage  | 
| Torsion | 
 L = 1 m, rotation angle ±180°, 10 cycles  | 
| Torsion acceptance criteria | 
 no damage  | 
| Impact resistance acceptance criteria | 
 Δα ≤ 0,05 dB after test, no damage  | 
| Torsion test method | 
 IEC 60794-1-21:E7  | 
| Impact resistance | 
 10 Nm, 3 impacts, d=20 mm, R=300 mm  | 
| Crush resistance - long term acceptance criteria | 
 Δα ≤ 0,05 dB prior release, no damage  | 
| Tensile performance - in service acceptance criteria | 
 Δα ≤ 0,05 dB  | 
| Tensile performance - in service test method | 
 IEC 60794-1-21:E1  | 
| Tensile performance - in service | 
 1400 N  | 
| Cable weight | 
 135.0 kg/km / 91 lbs/1000ft  | 
| Fiber type | 
 OM3  | 
| Cable type | 
 Stranded loose tube cable  | 
| Jacket material | 
 UV stable HDPE  | 
| Fiber Count | 
 192  | 
| CPR classification | 
 Fca  | 
| Armour | 
 Intensified rodent protection  | 
| Fiber color coding | 
 1.-12.: red, green, blue, yellow, white, grey, brown, violet, turquoise, black, orange, pink  | 
| Sheath marking | 
 Ink-Jet, white  | 
| Cable version | 
 n.a.  | 
| Application | 
 outdoor use  | 
| Loose tube diameter [mm] | 
 1.7  |