Operation temperature | -40 °C to +70 °C / -40 °F to +158 °F |
Temperature cycling acceptance criteria | Δα ≤ 0,05 dB |
Temperature cycling | -40 °C +70 °C / -40 °F +158 °F |
Temperature cycling test method | IEC 60794-1-22:F1 |
Transport / store temperature | -40 °C to +70 °C / -40 °F to +158 °F |
Crush resistance - short term | 4000 N/100mm |
Tensile performance - during installation | 8000 N |
Tensile performance - during installation acceptance criteria | Δα ≤ 0,05 dB after test |
Tensile Performance during Installation TestMethod | IEC 60794-1-21:E1 |
Repeated bending acceptance criteria | no damage |
Repeated bending test method | IEC 60794-1-21:E6 |
Repeated bending | R=20 x cable diameter, 25 cycles |
Cable bend - acceptance criteria | Δα ≤ 0,05 dB after test, no damage |
Torsion | L = 1 m, rotation angle ±180°, 10 cycles |
Torsion acceptance criteria | no damage |
Impact resistance acceptance criteria | Δα ≤ 0,05 dB after test, no damage |
Torsion test method | IEC 60794-1-21:E7 |
Impact resistance | 25 Nm, 3 impacts, d=20 mm, R=300 mm |
Crush resistance - long term acceptance criteria | Δα ≤ 0,05 dB prior release, no damage |
Cable weight | 670.0 kg/km / 449 lbs/1000ft |
Fiber type | OM4 |
Cable type | Stranded loose tube cable |
Cable design | Double jacket |
Jacket material | UV stable FRLSZH |
Fiber Count | 144 |
Inner jacket nominal thickness [mm] | 1.0000000000 mm |
CPR classification | Fca |
Armour | Steel wire armoured (SWA) |
Flammability - vertical cable bundle test method | EN 60332-3-22 (cat. A) |
Halogen free, acid gases | Pass |
Halogen free, Acid gases test method | EN 60754-2 |
Fiber color coding | 1.-12.: red, green, blue, yellow, white, grey, brown, violet, turquoise, black, orange, pink |
Sheath marking | Ink-Jet, black |
Smoke density | Pass |
Smoke density test method | EN 61034-1, EN 61034-2 |
FRP/coat. CSM nominal thickness [mm] | 2.5 / 6.7 |
Cable version | n.a. |
Application | universal use |
Loose tube diameter [mm] | 2.3 |