Steel wire armoured central loose tube cable with good mechanical protection and thus rodent protected.
The cable features a two jacket construction (inner on LDPE and outer on FRLSZH) with up to 24 fibers maximum and is suitable for indoor or outdoor duct or direct buried installation.
| DESCRIPTION | VALUE/VALUE RANGE | 
|---|---|
| Cable type | 
 Central loose tube cable  | 
| Jacket material | 
 UV stable FRLSZH  | 
| CPR classification | Fca | 
| Armour | 
 Steel wire armoured (SWA)  | 
| Cable design | 
 Double jacket  | 
| Fiber type | 
 G.652.D  | 
| Fiber Count | 6 | 
| Application | 
 universal-use  | 
| Cable family code | UX1ELWF | 
| DIN/VDE Code | U-DQ(ZN)2YBH wbg (R 0,63vzk) | 
| DoP no.: | D9030 | 
| Loose-tube count | 1 | 
| Fiber count per tube | 24 | 
| Loose tube nominal diameter [mm] | 3 mm | 
| Outer jacket nominal thickness [mm] | 1.3 mm | 
| Cable outer diameter [mm] | 9.9 mm | 
| Cable version | 
 n.a  | 
| Standard put-up length on drum | 2100 m ± 5% | 
| Halogen free, acid gases | 
 Pass  | 
| DESCRIPTION | VALUE/VALUE RANGE | 
|---|---|
| Cable weight | 170.0 kg/km / 114 lbs/1000ft | 
| Tensile performance - in service | 
 n.a.  | 
| Tensile performance - in service test method | 
 IEC 60794-1-21:E1  | 
| Tensile performance - in service acceptance criteria | 
 Δα ≤ 0,05 dB  | 
| Tensile performance - during installation | 
 4500 N  | 
| Tensile Performance during Installation TestMethod | 
 IEC 60794-1-21:E1  | 
| Tensile performance - during installation acceptance criteria | 
 Δα ≤ 0,05 dB after test  | 
| Crush resistance - long term | 
 2000 N/100mm  | 
| Crush resistance - long term test method | 
 IEC 60794-1-21:E3A  | 
| Crush resistance - long term acceptance criteria | 
 Δα ≤ 0,05 dB prior release, no damage  | 
| Impact resistance | 
 20 Nm, 3 impacts, d=20 mm, R=300 mm  | 
| Impact resistance test method | 
 IEC 60794-1-21:E4  | 
| Impact resistance acceptance criteria | 
 Δα ≤ 0,05 dB after test, no damage  | 
| Torsion | 
 L = 1 m, rotation angle ±180°, 10 cycles  | 
| Torsion test method | 
 IEC 60794-1-21:E7  | 
| Torsion acceptance criteria | 
 no damage  | 
| Cable bend | 
 d=20 x cable diameter, 4 turns, 3 cycles  | 
| Cable bend - test method | 
 IEC 60794-1-21:E11A  | 
| Cable bend - acceptance criteria | 
 Δα ≤ 0,05 dB after test, no damage  | 
| Repeated bending | 
 R=20 x cable diameter, 25 cycles  | 
| Repeated bending test method | 
 IEC 60794-1-21:E6  | 
| Repeated bending acceptance criteria | 
 no damage  | 
| DESCRIPTION | VALUE/VALUE RANGE | 
|---|---|
| Temperature cycling | -20 °C +70 °C / -4 °F +158 °F | 
| Temperature cycling - reversible | -30 °C +70 °C / -22 °F +158 °F | 
| Installation temperature | -5 °C +50 °C / +23 °F +122 °F | 
| Operation temperature | -20 °C to +70 °C / -4 °F to +158 °F | 
| Transport / store temperature | -30 °C to +70 °C / -22 °F to +158 °F |