Synergia logo

Central loose tube cable, fire-resistant, universal-use, SWA-steel wire armour, FRLSZH sheath - green, B2ca, 01x12-fibers OM3 (R856051)

Central loose tube cable, fire-resistant, universal-use, SWA-steel wire armour, FRLSZH sheath - green, B2ca, 01x12-fibers OM3 (R856051)

Central loose tube cable, fire-resistant, universal-use, SWA-steel wire armour, FRLSZH sheath - green, B2ca, 01x12-fibers OM3 (R856051)

Артикул: R856051 Категорія:
Environmental Characteristics

Operation temperature

-30 °C to +70 °C / -22 °F to +158 °F

Temperature cycling acceptance criteria

Δα ≤ 0,05 dB

Temperature cycling

-30 °C +70 °C / -22 °F +158 °F

Temperature cycling - reversible acceptance criteria

Δα ≤ 0,15 dB, reversible

Temperature cycling - reversible test method

IEC 60794-1-22:F1

Temperature cycling test method

IEC 60794-1-22:F1

Temperature cycling - reversible

-35 °C +70 °C / -31 °F +158 °F

Transport / store temperature

-35 °C to +70 °C / -31 °F to +158 °F

Mechanical Data

Crush resistance - short term

4000 N/100mm

Tensile performance - during installation

6000 N

Tensile performance - during installation acceptance criteria

Δα ≤ 0,05 dB after test

Tensile Performance during Installation TestMethod

IEC 60794-1-21:E1

Repeated bending acceptance criteria

no damage

Repeated bending test method

IEC 60794-1-21:E6

Repeated bending

R=20 x cable diameter, 25 cycles

Cable bend - acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Torsion

L = 1 m, rotation angle ±180°, 10 cycles

Torsion acceptance criteria

no damage

Impact resistance acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Torsion test method

IEC 60794-1-21:E7

Impact resistance

20 Nm, 3 impacts, d=20 mm, R=300 mm

Crush resistance - long term acceptance criteria

Δα ≤ 0,05 dB prior release, no damage

Tensile performance - in service acceptance criteria

Δα ≤ 0,05 dB

Tensile performance - in service test method

IEC 60794-1-21:E1

Tensile performance - in service

n.a.

Cable weight

185.0 kg/km / 124 lbs/1000ft

Technical Data

Fiber type

OM3

Cable type

Central loose tube cable

Cable design

Double jacket

Fiber Count

12

Inner jacket nominal thickness [mm]

1.0000000000 mm

CPR classification

B2ca

Armour

Steel wire armoured (SWA)

Fire resistance

Pass

Fire resistance test method

EN 60331-25 (180 min at 750°C)

Flammability - vertical cable bundle test method

EN 60332-3-22 (cat. A)

Halogen free, acid gases

Pass

Halogen free, Acid gases test method

EN 60754-2

Fiber color coding

1.-12.: red, green, blue, yellow, white, grey, brown, violet, turquoise, black, orange, pink13.-24.: red, green, blue, yellow, white, grey, brown, violet, turquoise, natural, orange, pink(ring-marked)

Sheath marking

Ink-Jet, black

Smoke density

Pass

Smoke density test method

EN 61034-1, EN 61034-2

Cable version

Fire-resistant

Application

universal use

Loose tube diameter [mm]

3

Prod

Маєте питання щодо товару, звертайтесь до нас:

 