Operation temperature | -30 °C to +70 °C / -22 °F to +158 °F |
Temperature cycling acceptance criteria | Δα ≤ 0,05 dB |
Temperature cycling | -30 °C +70 °C / -22 °F +158 °F |
Temperature cycling - reversible acceptance criteria | Δα ≤ 0,15 dB, reversible |
Temperature cycling - reversible test method | IEC 60794-1-22:F1 |
Temperature cycling test method | IEC 60794-1-22:F1 |
Temperature cycling - reversible | -35 °C +70 °C / -31 °F +158 °F |
Transport / store temperature | -35 °C to +70 °C / -31 °F to +158 °F |
Crush resistance - short term | 2000 N/100mm |
Tensile performance - during installation | 2000 N |
Tensile performance - during installation acceptance criteria | Δα ≤ 0,05 dB after test |
Tensile Performance during Installation TestMethod | IEC 60794-1-21:E1 |
Repeated bending acceptance criteria | no damage |
Repeated bending test method | IEC 60794-1-21:E6 |
Repeated bending | R=20 x cable diameter, 25 cycles |
Cable bend - acceptance criteria | Δα ≤ 0,05 dB after test, no damage |
Torsion | L = 1 m, rotation angle ±180°, 10 cycles |
Torsion acceptance criteria | no damage |
Impact resistance acceptance criteria | Δα ≤ 0,05 dB after test, no damage |
Torsion test method | IEC 60794-1-21:E7 |
Impact resistance | 10 Nm, 3 impacts, d=20 mm, R=300 mm |
Crush resistance - long term acceptance criteria | Δα ≤ 0,05 dB prior release, no damage |
Tensile performance - in service acceptance criteria | Δα ≤ 0,05 dB |
Tensile performance - in service test method | IEC 60794-1-21:E1 |
Tensile performance - in service | 800 N |
Cable weight | 58.0 kg/km / 39 lbs/1000ft |
Fiber type | OM4 |
Cable type | Central loose tube cable |
Jacket material | UV stable FRLSZH |
Fiber Count | 4 |
CPR classification | Dca |
Armour | Rodent protection |
Fire resistance | Pass |
Fire resistance test method | EN 60331-25 (180 min at 750°C) |
Flammability - vertical cable bundle test method | IEC 60332-3-22 |
Flammability - vertical single cable test method | IEC 60332-1-2 |
Halogen free, acid gases | Pass |
Halogen free, Acid gases test method | EN 60754-2 |
Sheath marking | Ink-Jet, black |
Smoke density | Pass |
Smoke density test method | EN 61034-1, EN 61034-2 |
Cable version | Fire-resistant |
Loose tube diameter [mm] | 2.3 |