Operation temperature | -20 °C to +60 °C / -4 °F to +140 °F |
Temperature cycling acceptance criteria | Δα ≤ 0,05 dB |
Temperature cycling | -20 °C +60 °C / -4 °F +140 °F |
Temperature cycling - reversible acceptance criteria | Δα ≤ 0,15 dB, reversible |
Temperature cycling - reversible test method | IEC 60794-1-22:F1 |
Temperature cycling test method | IEC 60794-1-22:F1 |
Temperature cycling - reversible | -25 °C +60 °C / -13 °F +140 °F |
Transport / store temperature | -25 °C to +60 °C / -13 °F to +140 °F |
Crush resistance - short term | 1000 N/100mm |
Tensile performance - during installation | 1000 N (5 min.) |
Tensile performance - during installation acceptance criteria | Δα ≤ 0,05 dB after test |
Tensile Performance during Installation TestMethod | IEC 60794-1-21:E1A |
Repeated bending acceptance criteria | no damage |
Kink | d=20 x cable diameter |
Repeated bending test method | IEC 60794-1-21:E6 |
Kink acceptance criteria | no kink |
Repeated bending | R=10 x cable diameter, 25 cycles, m = 4Kg |
Cable bend - acceptance criteria | no fiber breakage |
Torsion | L = 1 m, rotation angle ±180°, 10 cycles, F= 20N |
Torsion acceptance criteria | no fiber breakage |
Impact resistance acceptance criteria | no fiber breakage |
Torsion test method | IEC 60794-1-21:E7 |
Impact resistance | 5 Nm, 3 impacts, d=20 mm, R=12,5 mm |
Crush resistance - long term acceptance criteria | Δα ≤ 0,05 dB prior release, no damage |
Cable weight | 32.0 kg/km / 21 lbs/1000ft |
Fiber type | OM3 |
Cable type | gel-free indoor duct cable |
Jacket material | FRLSZH |
Fiber Count | 24 |
CPR classification | B2ca |
Armour | Rodent protection |
Fiber color coding | 1.-12.: red, green, blue, yellow, white, grey, brown, violet, turquoise, black, orange, pink13.-24.: red, green, blue, yellow, white, grey, brown, violet, turquoise, natural, orange, pink(ring-marked) |
Cable version | gel-free central loose tube |
Application | indoor use |
Loose tube diameter [mm] | 2.4 |