Environmental Characteristics

Operation temperature

-30 °C to 70 °C / -22 °F to +158 °F

Temperature cycling acceptance criteria

Δα ≤ 0,15 dB, reversible

Temperature cycling

-30 °C 70 °C / -22 °F +158 °F

Temperature cycling - reversible acceptance criteria

Δα ≤ 0,05 dB after test

Temperature cycling - reversible test method

IEC 60794-1-22:F1

Temperature cycling test method

IEC 60794-1-22:F1

Temperature cycling - reversible

-35 °C 70 °C / -31 °F +158 °F

Transport / store temperature

-35 °C to 70 °C / -31 °F to +158 °F

Mechanical Data

Crush resistance - short term

2000 N/100mm

Tensile performance - during installation

1800 N

Tensile performance - during installation acceptance criteria

Δα ≤ 0,05 dB after test

Tensile Performance during Installation TestMethod

IEC 60794-1-21:E1

Repeated bending acceptance criteria

no damage

Repeated bending test method

IEC 60794-1-21:E6

Repeated bending

R=20 x cable diameter, 25 cycles

Cable bend - acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Torsion

L = 1 m, rotation angle ±180°, 10 cycles

Torsion acceptance criteria

no damage

Impact resistance acceptance criteria

Δα ≤ 0,05 dB after test, no damage

Torsion test method

IEC 60794-1-21:E7

Impact resistance

10 Nm, 3 impacts, d=20 mm, R=300 mm

Crush resistance - long term acceptance criteria

Δα ≤ 0,05 dB prior release, no damage

Tensile performance - in service acceptance criteria

Δα ≤ 0,05 dB

Tensile performance - in service test method

IEC 60794-1-21:E1

Tensile performance - in service

600 N

Cable weight

45.0 kg/km / 30 lbs/1000ft

Technical Data

Fiber type

OM4

Cable type

Central loose tube cable

Jacket material

UV stable FRLSZH

Fiber Count

12

CPR classification

Dca

Armour

Intensified rodent protection

Flammability - vertical cable bundle test method

IEC 60332-3-22

Flammability - vertical single cable test method

IEC 60332-1-2

Fiber color coding

1.-12.: red, green, blue, yellow, white, grey, brown, violet, turquoise, black, orange, pink

Cable version

n.a.

Application

universal use

Loose tube diameter [mm]

2.3

Prod